Examine each carrier shell for cracks, dents, and stress fractures
ContextHold each carrier under direct light and rotate it slowly through all 360 degrees. Hairline cracks near the end caps or along the barrel seam are easy to miss but cause the carrier to split under the pressure differential, spraying contents — including blood tubes, medications, or pathology samples — inside the tube line. Any crack longer than 3mm or any visible deformation of the barrel warrants immediate retirement of that carrier. Mark it with red tape before pulling it from service to prevent accidental re-introduction into the fleet.